Brand Name : GFUVE

Model Number : LZCK720-10

Certification : IEC,ISO

Place of Origin : China

MOQ : 1 Pieces

Price : Negotiable

Payment Terms : T/T, Western Union,Paypal

Supply Ability : 10000 Pieces Per Month

Delivery Time : 3 - 7 Days

Packaging Details : Standard Export Wooden Box

Instrument security factor : FS≤10

Rated load : ≤10VA

Rated frequency : 50Hz or 60Hz

Rated secondary current : 5A or 1A

Weight (kg) : 2.1

Rated short-time thermal current : 40kA, 1S

Contact Now

1500/5A Resin Measuring and Protection Split Core Dry Type CT

This Model is is suitable forcurrent measurement and microcomputer protection of electrical equipment in 10KV and 35KV AC power system.

The transformer can be directly installed at the inlet andoutlet cables.The slice is imported silicon material. Thesemicircular ring core and secondary windings arevacuum poured by insulated resin.

Parameters

Technical parameters  
Standards IEC60044-1; IEC 61869-2; NTC 2205; ANSI C57.13; GB1208-2006
Rated primary current 100-1500A
Rated load ≤10VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Rated short-time thermal current 40kA, 1S
Rated continuous thermal current 120%I1n
Secondary winding power-frequency voltage 3kV, 1min
Instrument security factor FS≤10
Mechanical parameters  
Dimensions (W×D×H) (mm) φ80xφ110x50
Weight (kg) 2.1
Operating conditions  
Operating temperature -35°C to +55°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Altitude <3500 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

Datasheet

Type LZCK720-10 LZCK720-10
Purpose Measuring current transformer Protection current transformer
Ratio Accuracy class and rated load(VA) Accuracy class and rated load(VA)
I1/I2 0.5 1 10P10 10P5
100/1 2 2.5   1
200/1 2.5 3.75   2.5
300/1 3.75 5 2.5 3.75
400/1 5 7.5 3.75 5
500/1 7.5 10 5 7.5
600/1 10 15 7.5 10
100/5 2 2.5   1
200/5 2.5 3.75   2.5
300/5 3.75 5 2.5 3.75
400/5 5 7.5 3.75 5
500/5 7.5 10 5 7.5
600/5 10 15 7.5 10
800/5 10 15 7.5 10
1000/5 10 15 7.5 10
1200/5 10 15 7.5 10
1500/5 10 15 7.5 10

Outline Drawing

1500/5A Protection Split Core AC Current Sensor Dry Type Insulated Resin Poured


Product Tags:

donut type current transformer

      

split core current transducer

      
 1500/5A Protection Split Core AC Current Sensor Dry Type Insulated Resin Poured Manufactures

1500/5A Protection Split Core AC Current Sensor Dry Type Insulated Resin Poured Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)