Sign In | Join Free | My entremaqueros.com |
|
Brand Name : GFUVE
Model Number : GF312D1
Certification : CE, ISO9001
Place of Origin : BEIJING CHINA
MOQ : 1SET
Price : Negotiable
Payment Terms : L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability : 200SET/MONTH
Delivery Time : 2-3weeks
Packaging Details : Standard Export Box
Name : Handheld Three Phase Electric Meter Calibration and Testing of Power Engineering Devices
Accuracy : 0.05%, 0.1%
Relative humidity : 15%-85%
Resolution : 6”TFT (640×480)
Instrument Weight : 1.8kg
Harmonics : 2nd-64st
Handheld Three Phase Electric Meter Calibration and Testing of Power Engineering Devices
The instrument is a precision AC energy meter testing instrument, mainly used to test three phase energy meter error on site and measure all various of AC parameters.
Application
The devices used to calibrate electricity meters must be routinely verified themselves. That’s the only way to protect consumers. Laborelec’s working standards are well suited to the task. We can carry out calibration on your site, minimising disruption to your calibration routine.
Laborary has a fully equipped calibration equipment with the most accurate energy standard. It can furnish an extensive accreditation portfolio that is recognised internationally.
FEATURES
PARAMETERS
Electrical parameters | |
Accuracy class | 0.05%, 0.1% |
Resolution | 6”TFT (640×480) |
Power supply | 220V±10%, 50/60Hz Li-polymer battery (size (mm): 110x51x16, nominal output voltage: 7.2V, capacity: 5000mAh) Power line supply (U1, UN), 85V-265V 50/60Hz |
Communication port | RS232 |
Test voltage | |
Range | 0-480V |
Error | ±0.05% (30V-480V) |
±0.1% (5V-30V) | |
Harmonic | 2nd-64st |
Test current | |
Range (direct connection) | 5mA-20A |
Error (direct connection) | ±0.05% (100mA-20A) ±0.1% (10mA-100mA) |
Range (clamp CT) | 10mA-3000A |
Error (camp CT) | ±0.2% (100mA-100A) ±0.5% (100A-3000A) |
Harmonic | 2nd-64st |
Power measure error | |
Active power (direct connection) | ±0.05% (0.1A-20A) ±0.1% (0.01A-0.1A) |
Reactive power (direct connection) | ±0.1% (0.1A-20A) |
Energy measure error | |
Active energy (direct connection) | ±0.05% (0.1A-20A) ±0.1% (0.01A-0.1A) |
Reactive energy (direct connection) | ±0.1% (0.1A-20A) |
Phase angle | |
Range | 0o-360o |
Resolution | 0.01o |
Error | ±0.05o |
Frequency | |
Range | 45-65Hz |
Resolution | 0.001Hz |
Error | 0.002Hz |
Pulse input | |
Input channel | 2 |
Input level | 5-24V |
Input frequency | Max. 2MHz |
Pulse output | |
Energy constant | 180000imp/kWh, 1800imp/kWh, 180imp/kWh |
Pulse ratio | 1:1 |
Output level | 5V |
Function | |
Vector diagram | Yes |
Waveform | Yes |
Energy accumulation | Yes |
Communication with PC | Yes |
Mechanical parameters | |
Instrument dimensions (W×H×D) (mm) | 245×162×60 |
Instrument Weight (kg) | 1.8 |
Carry case dimensions (W×H×D) (mm) | 450×320×185 |
Carry case (kg) | 10.6 |
Environmental conditions | |
Ambient temperature | -10°C to 55°C |
Relative humidity | 15%-85% |
![]() |
Handheld Electrical Test Meter Calibration Durable Power Engineering Devices Images |