Sign In | Join Free | My entremaqueros.com |
|
Brand Name : GFUVE
Model Number : GF302D
Certification : CE,IOS9001
Place of Origin : Beijing,China
MOQ : 1 SET
Payment Terms : T/T, Western Union
Supply Ability : 100+SET+per month
Delivery Time : 5-8 work days
Packaging Details : Standard wooden package
Accuracy : 0.02%,0.05%, 0.1%
Voltage output : 0-500V
Current output : 0-120A
Harmonic : 2-51st
Phase Output : 0°-359.999°
Power Factor : -1 ~ 0 ~ 1
Frequency Output : 45Hz-65Hz
Standard configuration : Optical sampler
Optional : PC software
HMI : Touch color screen,RS232
Meter position : 1 or 3
Warranty : 36 months
The Portable Three Phase kWh Meter test equipment is used for grid corporation of measurement and energy test center, management department of power supply bureau, national energy measurement of testing authorities, and also used to test each kind of single/three phase kWh meter of industries and mining enterprises as well as electric meter manufacturers. Meanwhile, the calibrator also can be used as one high precision standard power source.
Electrical parameters | |
---|---|
Accuracy | 0.05%, 0.1% |
Power Supply | One Phase AC 180-265V, frequency 50/60Hz. |
AC Voltage Output | |
Range(U1,U2,U3) | 57.7V, 100V, 220V, 380V or 69.3V, 120V, 240V, 480V( optional) |
Adjustment range | (0-120)%RG(1) |
Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability | 0.01%/120s |
Distortion | 0.3% (Non-capacitive load) |
Output load | each phase 25VA |
Measuring accuracy | 0.05%RG |
AC Current Output | |
Range(I1,I2,I3) | 200mA, 1A, 5A, 20A, 100A |
Adjustment range | (0-120)%RG |
Adjustment fineness | 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional. |
Stability | <0.01%/120s |
Distortion | ≤0.3% (Non-capacitive load) |
Output load | 45VA |
Accuracy | 0.05%RG |
Power Output | |
Active power output stability | <0.01%RG/120s |
Reactive power output stability | <0.02%RG/120s |
Active power measuring accuracy | 0.05%RG |
Reactive power measuring accuracy | 0.1%RG |
Phase Output | |
Output adjustment range | 0°-359.999° |
Output adjustment fineness | 10, 1, 0.1, 0.01 as optional. |
Resolution | 0.01° |
Accuracy | 0.05° |
Power Factor | |
Adjustment range | -1 ~ 0 ~ 1 |
Resolution | 0.0001 |
Measurement accuracy | 0. 0005 |
Frequency Output | |
Adjustment range | 45Hz-65Hz |
Output adjustment fineness | 5Hz, 1Hz, 0.1Hz, 0.01Hz as optional. |
Resolution | 0.001Hz |
Accuracy | 0.005Hz |
Voltage /Current/Harmonic Setting | |
Harmonic number | 2-51times |
Harmonic content | 0-40% |
Harmonic phase | 0-359.99 |
Harmonic setting accuracy | (10%±0.1%)RD(2) |
Power Energy Measurement Error | |
Active power energy | 0.05%RG |
Reactive power energy | 0.1%RG |
Power Pulse Output | |
Power pulse type | active pulse, reactive pulse |
Active power pulse output | 5V, 10mA |
Power Pulse Input | |
Energy pulse type | support active and reactive pulse, the highest frequency power pulse input is 180K. |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 500x600x175 |
Weight (kg) | About 27 |
(1) RG means range, the same as below; (2) RD means the setted harmonic content, harmonic can be a single output, also multiple output. |
![]() |
Portable Electrical Test Meter Calibration Electrical Equipment Calibration Multiple Output Images |